WAGO-I/O-SYSTEM 750
Commissioning 95
750-363/0040-0000 FC EtherNet/IP G4 ECO XTR
Manual
Version 1.0.0
Table 40: Address selection switch values (host ID)
Address selection switch Description
1 … 254
Address selection switch is enabled.
The host ID is set to a fixed value between 1 ... 254.
The IP address consists of the static base address
and the set host ID. The IP address set via the
current device configuration (DHCP, BootP, static) is
disabled.
0
Address selection switch is disabled.
The IP address set via the current device
configuration (DHCP, BootP, static) is used.
255
Address selection switch is disabled.
The IP address is obtained from a DHCP server.
More information about changing the static base address
You can also change the static base address currently saved in the fieldbus
coupler/controller as required. Proceed as described for example in the section
“Assigning IP Address via “WAGO Ethernet Settings””.
1.
To configure the IP address via the address selection switch by setting the
host ID (last position of the IP address) to a value that does not equal
0/255, first convert the host ID to the binary representation.
For example, host ID “50” results in a binary code of “00110010”.
2.
Set the bits in sequence using the 8 address switches. Start with address
switch 1 to set bit 0 (LSB) and end with address switch 8 for bit 7 (MSB).
Figure 44: Address Selection Switch, for Example the Value Setting “50” (2
1
+ 2
4
+ 2
5
)
3.
Restart the fieldbus node after adjusting the address selection switch to
apply the configuration changes.