Table 59: Blink code- table for the I/O LED signaling, error code 1
Error code 1: "Hardware and configuration error"
Error
Argument
Error Description
Solution
9
Head station
initialization error
1. Turn off the power supply of the node.
2. Replace the head station.
3. Turn on again the power supply of the node.
10 ... 13
not used
14
Maximum number of
gateway or mailbox
modules exceeded
1. Turn off the power supply of the node.
2. Reduce the number of corresponding modules to a valid
number.
3. Turn on again the power supply of the node.
15
Firmware loader was
loaded from backup.
1. Execute the last firmware update again.
2. If the error persists, contact I/O support.
16
Firmware was loaded
from backup.
1. Execute the last firmware update again.
2. If the error persists, contact I/O support.
Table 60: Blink Code Table for the I/O LED Signaling, Error Code 2
Error Code 2: „Process image exceeded“
Error
Argument
Error Description
Solution
1
Not used
-
2
Maximum process
image size
exceeded
1. Turn off the power supply of the node.
2. Reduce number of I/O modules.
3. Turn on again the power supply of the node.
3
Process image
generation error
1. Turn off the power supply of the node.
2. Remove unsupported I/O modules.
3. Turn on again the power supply of the node.