178 Fieldbus Communication
WAGO-I/O-SYSTEM 750
750-363/0040-0000 FC EtherNet/IP G4 ECO XTR
Manual
Version 1.0.0
Instance 1
Table 107: TCP/IP interface (F5
hex
) – Instance 1
Attribute ID Acces
s
NV Name
Data type Description
Default
value
1
Get
V
Status
DWORD Interface state
-
2
Get
V
Configuration
Capability
DWORD Interface flags for possible
kinds of configuration
0x00000017
3
Set
NV Configuration
Control
DWORD Specifies, how the device gets
is TCP/IP configuration after
the first Power On
0x00000011
4
Get
V
Physical Link
Object
STRUCT
of
Path size
UINT
Number of 16 Bit words in the
following path
0x0002
Path
Padded
EPATH
Logical path, which points to
the physical Link object
0x20 0xF6
0x24 0x03
(equates to
the Ethernet
Link Object)
5
Set
NV Interface
Configuration
STRUCT
of
-
IP Address
UDINT
IP address
0
Network Mask UDINT
Net work mask
0
Gateway
Address
UDINT
IP address of default gateway 0
Name Server UDINT
IP address of the primary
name of the server
0
Name Server
2
UDINT
IP address of the secondary
name of the server
0
Domain Name STRING
Default domain name
“”
6
Set
NV Host Name
STRING
Device name
“”
10
Set
NV SelectAcd
BOOL
Enable (1) or disable (0) the
automatic IP address conflict
detection via ACD
1 (0x01)
11
Set
NV LastConflictD
etected
STRUCT
of:
Last detected IP address
conflict
AcdActivity
USINT
Status of activity of ACD
0 (0x00)
RemoteMAC ARRAY of
6 USINT
MAC ID oft he conflicting
device
0x00, …
0x00
ArpPdu
ARRAY of
28 USINT
Copy of the ARP PDU that
caused the conflict
0x00, …,
0x00
13
Set
NV Encapsulation
Inactivity
Timeout
UINT
Timeout in seconds for
encapsulation sessions
120
(0x0078)