WAGO-I/O-SYSTEM 750 Configuring via the Web-Based Management System (WBM) 121
750-363/0040-0000 FC EtherNet/IP G4 ECO XTR
Manual
Version 1.0.0
Table 46: WBM page "Storage Media"
Local Disks
Entry
Value (Example) Description
Drive Letter
A
Directory
Total Size [kB]
1050184 kB
Total size of the file system
Used Size [kB]
295560 kB
Used memory capacity
Free Size [kB]
754624 kB
Free memory capacity
File System
FAT
File system (File Allocation Table)
9.9
Update
Use the “Update“ WBM page to update the firmware of the device. To do this, the
associated firmware image is first selected from the PC's local file system and
downloaded to the device. Afterwards, the update will be executed and the
device will be restarted automatically.
After the firmware update, the WBM pages will also be updated, self-created
HTML pages or settings will be remained save.
Stop fieldbus application and finish FTP connections before the update !
Please ensure, that the superordinate fieldbus application has been stopped and
possibly existing FTP connections has been finished before starting the update
process. When the software reset is beeing executed, the connection to the web-
based management will be lost and the web-page has to be reloaded.
Table 47: WBM Page “Update“
Firmware Selection / Upload
Entry
Button
Value
(example)
Description
Firmware image
[Durchsuchen…]
firmware.bin
Use this button to select the firmware
image file on your local file system (PC).
[UPLOAD]
OK
This button loads the previously selected
firmware image file from your local file
system to the device.
Update Status
-
Verification of
firmware image
is done
Status display for the update.
Button
Description
[RESET]
Resetting the upload status (e.g. when selecting a wrong
image file).
[UPDATE]
With this button you start the update process.
The firmware image file previously loaded on the device is first
checked and then installed.
Afterwards an automatic restart of the device takes place.