WAGO-I/O-SYSTEM 750
Fieldbus Communication 187
750-363/0040-0000 FC EtherNet/IP G4 ECO XTR
Manual
Version 1.0.0
120 (0x78)
Set
NV Bk_Header
CfgOT
UINT
Indicates whether the
RUN/IDLE header is used
originator
target direction
0: is used
1: is not used
0x0000
121(0x79)
Set
NV Bk_Header
CfgTO
UINT
Indicates whether the
RUN/IDLE header is used
originator
target direction
0: is used
1: is not used
0x0001
Common Service
Table 116: Coupler/Controller configuration (64
hex
) – Common service
Service code Service
available
Service name
Description
Class Instance
0E
hex
Yes
Yes
Get_Attribute_Single Supplies contents of the appropriate attribute
10
hex
No
Yes
Set_Attribute_Single Modifies an attribute value
11.2.5.11 Discrete Input Point (65
hex
)
This class allows the reading of data of a particular digital input point.
Instance 0 (Class-Attributes)
Table 117: Discrete input point (65
hex
) – Class
Attribute ID Acces
s
Name
Data type Description
Default value
1
Get
Revision
UINT
Revision of this object
1 (0x0001)
2
Get
Max Instance
UINT
Max. number of instances
-
3
Get
Number of
Instances
UINT
Number of Instances
-
Instance 1 ... 255 (Digital output value 1 up to 255)
Table 118: Discrete input point (65
hex
) – Instance 1...255
Attribute ID Acces
s
Name
Data type Description
Default value
1
Get
DipObj_Value
BYTE
Digital output (only Bit 0 is valid)
-
Common Services
Table 119: Discrete input point (65
hex
) – Common service
Service code Service
available
Service name
Description
Class Instance
0E
hex
Yes
Yes
Get_Attribute_Single Supplies contents of the appropriate attribute