![WAGO 750-363/0040-0000 Скачать руководство пользователя страница 38](http://html1.mh-extra.com/html/wago/750-363-0040-0000/750-363-0040-0000_manual_868425038.webp)
38 System Description
WAGO-I/O-SYSTEM 750
750-363/0040-0000 FC EtherNet/IP G4 ECO XTR
Manual
Version 1.0.0
Re-establish the ground connection when the connection to the power
jumper contacts is disrupted!
Some I/O modules have no or very few power contacts (depending on the I/O
function). Due to this, the passing through of the relevant potential is disrupted. If
you require a field supply via power jumper contacts for subsequent I/O modules,
then you have to use a power supply module.
Note the data sheets of the I/O modules.
Use a spacer module when setting up a node with different potentials!
In the case of a node setup with different potentials, e.g. the alteration from
24 VDC to 230 VAC, you should use a spacer module. The optical separation of
the potentials acts as a warning to heed caution in the case of wiring and
maintenance works. Thus, you can prevent the results of wiring errors.