WAGO-I/O-SYSTEM 750
System Description 33
750-363/0040-0000 FC EtherNet/IP G4 ECO XTR
Manual
Version 1.0.0
Figure 8: Field supply (sensor/actuator) (example)
Table 7: Legend for the “Field supply (sensor/actuator)” figure
Position Beschreibung
1
Field supply 24 VDC
2
Field supply 0 V
3
Power jumper contacts (potential distribution to adjacent I/O modules)
In exceptional instances, I/O modules can be directly connected to the
field supply!
The 24 V field supply can be connected also directly to a bus module, if the
connection points are not needed for the peripheral device supply. In this case,
the connection points need the connection to the power jumper contacts.
The field-side power supply is automatically derived from the power jumper
contacts when snapping an I/O module.
The current load of the power contacts must not exceed 10 A on a continual
basis.
By inserting an additional power supply module, the field supply via the power
contacts is disrupted. From there a new power supply occurs which may also
contain a new voltage potential.
3.4.4.2 Fusing via Power Supply Module
Internal fusing of the field supply is possible for various field voltages via an
appropriate power supply module.