WAGO-I/O-SYSTEM 750
Commissioning 109
750-363/0040-0000 FC EtherNet/IP G4 ECO XTR
Manual
Version 1.0.0
8.7
Synchronizing the System Time
The head station’s system time enables a date and time indication for files in the
flash file system.
System time will be reset when the fieldbus node is de-energized!
The head station 750-363/0040-0000 does not have a real-time clock. For this
reason, the current system time will be reset when the fieldbus node is de-
energized!
After switching on the operating voltage, the system time starts at 01/01/2000,
00:00:00 a.m.
At start-up, synchronize the system time with the computer’s current time.
There are two options to synchronize the system time:
•
Synchronize the system time using “
WAGO Ethernet Settings
”
•
Synchronize the system time using the
Web Based Management System
Synchronize the system time using “WAGO Ethernet Settings”
Do not set time during a WAGO I/O-
CHECK
communication!
Note that setting the clock during a WAGO I/O-
CHECK
communication may
cause communication errors. Therefore set the time only if WAGO I/O-
CHECK
is
not yet started.
1.
Switch off the supply voltage of the fieldbus node.
2.
Connect the communication cable 750-920 or 750-923 respectively the
Bluetooth
®
Adapter 750-921 to the service interface of the head station of
the fieldbus node and to your computer.
3.
Switch on the supply voltage of the fieldbus node.
The head station is initialized. The head station determines the I/O module
configuration of the fieldbus node and creates a process image.
During start-up, the I/O LED (red) flashes.
If the I/O LED lights up green after a brief period, the fieldbus node is operational.
If an error occurs during start-up indicated by the I/O LED flashing red, evaluate
the error code and argument and resolve the error.