106 Commissioning
WAGO-I/O-SYSTEM 750
750-363/0040-0000 FC EtherNet/IP G4 ECO XTR
Manual
Version 1.0.0
8.5
Testing the Function of the Fieldbus Node
1.
To ensure that the IP address is correct and to test communication with the
fieldbus node, first turn off the operating voltage of the fieldbus node.
2.
Create a non-serial connection between your PC and the fieldbus node.
The head station is initialized. The head station determines the I/O module
configuration of the fieldbus node and creates a process image.
During start-up, the I/O LED (red) flashes.
If the I/O LED lights up green after a brief period, the fieldbus node is operational.
If an error occurs during start-up indicated by the I/O LED flashing red, evaluate
the error code and argument and resolve the error.
More information about LED signaling
The exact description for evaluating the LED signal displayed is available in the
section “Diagnostics” > … > “LED Signaling”.