WAGO-I/O-SYSTEM 750
I/O Modules 203
750-363/0040-0000 FC EtherNet/IP G4 ECO XTR
Manual
Version 1.0.0
12.2.1 Digital Input Modules
The digital input modules provide a process value of one bit per channel, which
indicates the status of the respective channel. These bits are mapped into the
input process image.
Some digital input modules have an additional diagnostic bit per channel in the
input process image. The diagnostic bit detects faults (e.g., wire breakage,
overloads and/or short circuits).
If analog input modules are in the node, the digital data is grouped in bytes and
added to the analog input data in the process image. 1 sub-index is assigned for
each 8 bit.
Each input channel occupies on instance in the “Discrete Input Point Object”
(Class 0x65).
12.2.1.1 1-Channel Digital Input Modules with Diagnostics
Table 171: 1-channel digital input modules with diagnostics
Input process image
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
Diagnostic
bit
S 1
Data bit
DI 1
The input modules occupy 2 instances in class (0x65).
12.2.1.2 2-Channel Digital Input Modules
Table 172: 2-channel digital input modules
Input process image
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
Data bit
DI 2
Channel 2
Data bit
DI 1
Channel 1
The input modules occupy 2 instances in class (0x65).
12.2.1.3 2-Channel Digital Input Modules with Diagnostics
Table 173: 2-channel digital input modules with diagnostics
Input process image
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
Diag. bit S 2
Channel 2
Diag. bit S 1
Channel 1
Data bit
DI 2
Channel 2
Data bit
DI 1
Channel 1
The input modules occupy 4 instances in class (0x65).
12.2.1.4 2-Channel Digital Input Modules with Diagnostics and Output Data
In addition to process values for input process image, the digital input modules
provide 4 bits of data in the output process image.