11.2.5.22 Analog Input Point Extended 3 (73
hex
)
The extension of the “Analog Input Point” class enables the reading of data from
a fieldbus node that contains over 765 analog outputs (AIPs). The instance scope
of the “Analog Input Point Extended 3” class covers AIPs from 766 to 1020 in the
fieldbus node.
Instance 0 (Class Attributes)
Table 150: Analog Input Point Extended 3 (73
hex
) – Class
Attribute ID Access Name
Data type Description
Default
value
1
Get
Revision
UINT
Revision of this object
1 (0x0001)
2
Get
Max Instance
UINT
Max. number of instances
-
3
Get
Number of
Instances
UINT
Number of Instances
-
Instance 1 ... 255 (Analog input value 766 up to 1020)
Table 151: Analog Input Point Extended 3 (73
hex
) – Instance 766 ... 1020
Attribute ID Access Name
Data type Description
Default
value
1
Get
AipObj_Value
ARRAY of
BYTE
Analog Input
-
2
Get
AipObj_Value_L
ength
USINT
Length of the output data
AopObj_Value (in byte)
-
Common Services
Table 152: Analog Input Point Extended 3 (73
hex
) – Common service
Service
code
Service available
Service name
Description
Class Instance
0E
hex
Yes
Yes
Get_Attribute_Single Supplies contents of the appropriate
attribute
11.2.5.23 Analog Output Point (68
hex
)
This class enables the reading of data of a particular analog output point (AOP).
An analog output point is part of an analog output module.
Instance 0 (Class Attributes)
Table 153: Analog Output Point (68
hex
) – Class
Attribute ID Access Name
Data type Description
Default
value
1
Get
Revision
UINT
Revision of this object
1 (0x0001)
2
Get
Max Instance
UINT
Max. number of instances
-
3
Get
Number of
Instances
UINT
Number of Instances
-