Table 110: Ethernet link (F6
hex
) – Instance 1
Attribute ID Acces
s
NV Name
Data type Description
Default value
1
Get
NV Interface Speed UDINT
Transfer rate
100
(0x00000064)
2
Get
NV Interface Flags
DWORD Interface configuration
and status information
Bit 0: Link status
Bit 1: Half/full duplex
Bit 2…4: Detection
status
Bit 5: Manual settings
require reset
Bit 6: Local hardware
error
Bit 7…31: Reserved
Value is
dependent upon
Ethernet
connection.
3
Get
NV Physical Address
ARRAY of
6 UINTs
MAC layer address
MAC ID of the
device
6
Set
NV Interface Control STRUCT
of:
Configuration of the
physical interface
-
Control Bits
WORD
Interface configuration
bits
Bit 0: Automatic
detection
Bit 1: Default duplex
mode
Bit 2…15: Reserved
0x0001
Forced Interface
Speed
UINT
Preset interface speed 0 (0x0000) –
Auto negotiate
7
Get
NV Interface Type
USINT
Interface type
Value 0: Unknown
Value 1: Internal
interface; e.g., in the
case of an integrated
switch
Value 2: Twisted pair
(e.g. 100Base-TX).
Value 3: fiber glass
(e.g. 100Base-FX).
Value 4…256:
Reserved
2 (0x02) –
Twisted Pair
8
Get
NV Interface State
USINT
Interface status
Value 0: Unknown
Value 1: Interface
active and ready to
send/receive.
Value 2: Interface
deactivated.
Value 3: Interface is
testing
Wert 4…256: