79 LON communication module: Fault manager
Display
Value
Explanations
Displayed only if parameter "76:1" has been set.
Note
Only one control unit may be programmed as fault
manager.
Control unit is not fault manager
79:0
Control unit is fault manager
79:1
7B LON communication module: Time
Display
Value
Explanations
Displayed only if parameter "76:1" has been set.
Control unit does not transmit the time.
7B:0
Control unit transmits the time.
7B:1
80 Fault messaging delay
Display
Value
Explanations
30 s
80:6
A fault message is issued if a fault is present for at
least 30 s.
... s
80:0 to
80:199
Delay adjustable from 0 to 995 s
1 step
≙
5 s
81 Automatic summer/wintertime changeover
!
Display
Value
Explanations
Without
81:0
Time must be changed manually.
With
81:1
With automatic summer/wintertime changeover
No application
81:2
Do not adjust
With LON communication module: Control
unit receives the time
81:3
82 Summer time starts: Month
!
Display
Value
Explanations
Displayed only if parameter "81:1" has been set.
The selected value denotes the relevant month
"1"
= January
"12" = December
March
82:3
Relevant month
82:1 to
82:12
Parameter
General
(cont.)