61
34 Run-on time for circulation pump, neutralising system at output 2 at AM1 extension
Display
Value
Explanations
■
Displayed only if parameter "30:1" has been set.
■
Requirement: Code/parameter "32:3" must be set.
None
34:0
... s
34:0 to
34:255
40 Extension EA1
Display
Value
Explanations
Without
40:0
With
40:1
Recognised automatically.
41 Function, output 157 at extension EA1
Display
Value
Explanations
Displayed only if parameter "40:1" has been set.
Central fault message
41:0
Feed pump
41:1
Only in conjunction with Vitocontrol
DHW circulation pump
41:2
Do not adjust
Heating circuit pump, HC 1 on low speed
41:3
Do not adjust
Heating circuit pump, HC 2 on low speed
41:4
Do not adjust
Heating circuit pump, HC 3 on low speed
41:5
Do not adjust
42 Function, input DE1 at extension EA1
Display
Value
Explanations
Displayed only if parameter "40:1" has been set.
None
42:0
Operating program changeover
42:1
Do not adjust
External demand with set flow temperature
42:2
External blocking
42:3
External blocking and fault message
42:4
External fault message
42:5
Brief operation, DHW circulation pump
(pushbutton function)
42:6
Do not adjust
Parameter
General
(cont.)