79
0C Delta T monitoring
Display
Value
Explanations
OFF
0C:0
ON
0C:1
No flow rate captured in the solar circuit, or flow rate
too low.
0D Night DHW circulation monitoring
Display
Value
Explanations
OFF
0D:0
ON
0D:1
Unintentional flow rate in the solar circuit (e.g. at
night) is captured.
0E Calculation of solar yield
Display
Value
Explanations
OFF
0E:0
Calculation of solar yield with Viessmann
heat transfer medium
0E:1
Calculation of solar yield with water as heat
transfer medium
0E:2
Do not adjust
0F Flow rate, solar circuit at max. pump speed
Display
Value
Explanations
7 l/min
0F:70
... l/min
0F:1 to
0F:255
Flow rate adjustable from 0.1 to 25.5 l/min
1 step
≙
0.1 l/min
10 Target temperature control
Display
Value
Explanations
OFF
10:0
ON
10:1
See parameter "11"
11 Set DHW temperature, solar
Display
Value
Explanations
■
Target temperature control is switched on (parame-
ter "10:1"):
Temperature at which the solar heated water is to be
stratified into the DHW cylinder.
■
Heating of 2 DHW cylinders is set (parameter
"20:9"):
When the set cylinder temperature is achieved in
one DHW cylinder, the 2nd DHW cylinder is heated.
50 °C
11:50
... °C
11:10 to
11:90
Set solar cylinder temperature adjustable from 10 to
90 °C.
Parameter
Solar
(cont.)
5863679
Parameter