74
2D Shunt pump
Display
Value
Explanations
Shunt pump ON only in case of demand
2D:0
Note
Temperature for demand depends on coding card
Constantly ON
2D:1
Domestic hot water
Parameter values in
bold
are factory settings.
00 Tank heating
!
Display
Value
Explanations
See chapter "Function description"
Hysteresis
±
2.5 K
00:0
Adaptive tank heating enabled
00:1
Tank temperature control with 2 tempera-
ture sensors
00:2
Tank temperature control, tank loading sys-
tem
00:3
01 Selection of set DHW temperature
Display
Value
Explanations
Note
Observe the maximum permissible DHW temperature.
10 °C .. 60 °C
01:0
Set DHW temperature adjustable from 10 to 60 °C
10 °C .. 95 °C
01:1
Set DHW temperature adjustable from 10 to 95 °C
03 Additional function for increased DHW heating
Display
Value
Explanations
No 2nd set cylinder temperature
03:0
Additional function cannot be enabled.
No 2nd set cylinder temperature
03:0 to
03:9
Additional function cannot be enabled.
... °C
03:10 to
03:95
Entry of a 2nd set cylinder temperature
Adjustable from 10 to 95 °C
Note parameter "01" setting.
Activate additional function by setting parameter "09".
04 Cylinder heating: Set start point
Display
Value
Explanations
2.5 K below set value
04:0
Set start point
–
2.5 K
Set stop point +2.5 K
... K below set value
04:1 to
04:10
Adjustable from 1 to 10 K below set value
Parameter
Boiler
(cont.)
5863679
Parameter