75
05 Set flow temperature for cylinder heating
Display
Value
Explanations
Set system flow temperature
05:0
The set flow temperature is determined by the highest
system flow temperature demand.
Max. set system flow temperature for DHW
heating
05:1
The set flow temperature is determined by the cylinder
flow temperature demand.
06 Differential, set boiler water temperature to set DHW temperature
Display
Value
Explanations
20 K if the set boiler water temperature is
above the set cylinder temperature
06:20
During DHW heating, the boiler water temperature is
at least 20 K higher than the set DHW temperature.
... K if the set boiler water temperature is
above the set cylinder temperature
06:0 to
06:50
Differential between the boiler water temperature and
the set DHW temperature
Adjustable from 0 to 50 K
07 Circulation pump for cylinder heating
Display
Value
Explanations
The circulation pump for tank heating starts
depending on the boiler water temperature
07:0
Not effective if parameter "00:3" has been set.
Started immediately.
07:1
08 Circulation pump run-on
Display
Value
Explanations
10 min
08:10
Circulation pump with max 10 min run-on time after
cylinder heating
No run-on
08:0
No circulation pump run-on
... min
08:1 to
08:15
09 Frequency, auxiliary function for DHW heating
Display
Value
Explanations
Without
09:0
Daily
09:1
Every 2 to 14 days
09:2 to
09:14
2 x daily
09:15
Parameter
Domestic hot water
(cont.)
5863679