76
0C For solar DHW heating: DHW temperature target
!
Display
Value
Explanations
Reheating is suppressed above the selected set tem-
perature (DHW heating by the boiler only if solar en-
ergy is insufficient).
Note parameter "01" setting.
40 °C
0C:40
Set DHW temperature 40 °C
None
0C:0 to
0C:9
No set value 3
... °C
0C:10 to
0C:95
Entry of a 2nd set DHW temperature
0D With 2 tank temperature sensors: Tank heating stop point
Display
Value
Explanations
Displayed only if parameter "00:2" has been set.
...
0D:8
Cylinder heating stop point at set value x 0.8
...
0D:2 to
0D:10
Adjustable from 0.2 to 1
1 step
≙
0.1
0E With 2 tank temperature sensors: Tank heating start point
Display
Value
Explanations
Displayed only if parameter "00:2" has been set.
...
0E:7
Cylinder heating stop point at set value x 0.7
...
0E:1 to
0E:9
Adjustable from 0.1 to 0.9
1 step
≙
0.1
0F Runtime, actuator, mixing valve, heat exchanger set, Vitotrans 222
Display
Value
Explanations
Displayed only if parameter "00:3" has been set.
75 s
0F:75
... s
0F:10 to
0F:255
11 Runtime, primary cylinder loading pump, heat exchanger set
Display
Value
Explanations
Displayed only if parameter "00:3" has been set.
Cycling of the secondary cylinder loading pump for
the cylinder loading system in the start phase of the
system.
Setting is subject to the type of circulation pump (con-
nection at plug
sA
)
10 s
11:10
The secondary cylinder loading pump for the cylinder
loading system is switched on cyclically for 10 s.
... s
11:0 to
11:30
Parameter
Domestic hot water
(cont.)
5863679
Parameter