63
52 Sensor 17B
Display
Value
Explanations
Not installed
52:0
Available
52:1
Recognised automatically.
53 Connection at plug 20A1
Display
Value
Explanations
Note
Factory setting, according to coding card
Heating circuit pump
53:0
Do not adjust
Primary cylinder loading pump for heat ex-
changer set
53:1
Therm-Control
53:2
Switching contact, Therm-Control
Circulation pump – flue gas/water heat ex-
changer
53:3
54 Connection at plug 29
Display
Value
Explanations
Note
Factory settings, according to coding card
Distribution pump
54:0
Do not adjust
Shunt pump
54:1
Boiler circuit pump
54:2
Boiler circuit pump with butterfly valve func-
tion
54:3
55 Connection at plug 52A1
Display
Value
Explanations
Note
Factory settings, according to coding card
Butterfly valve
55:0
Mixing valve for return temperature control
55:1
Mixing valve, heat exchanger set
55:2
Do not adjust
55:3
56 Runtime, servomotor, butterfly valve/return temperature control
!
Display
Value
Explanations
125 s
56:125
... s
56:5 to
56:199
Parameter
General
(cont.)