56
There are 2 parameter levels:
■
Parameter level 1
The most frequently used parameters are listed here.
These parameters are marked with
!
.
■
Parameter level 2
All
parameters are included here, including those of
parameter level 1.
Calling up parameter levels
■
Parameters are displayed according to system ver-
sion: See page 14.
■
The parameters are split into groups.
Tap the following buttons:
0
1.
0
2. "Service"
0
3.
Enter the password "viservice".
0
4. "System configuration"
0
5. "Parameter level 1"
or
"Parameter level 2"
Enter the password "viexpert".
0
6.
Select group.
0
7.
Use
or
to select the parameter.
0
8.
0
9.
Use
or
for the required value in line with
the tables below
10.
Use
to confirm.
Parameter groups
Single boiler system
Multi boiler system
■
General
■
Boiler
■
DHW
■
Solar
■
General
■
Boiler
Resetting parameters to their delivered condition
This also resets the parameters in the other parameter
level.
Tap the following buttons:
1.
2. "Service"
3.
Enter the password "viservice".
4. "System configuration"
5. "Parameter level 1"
or
"Parameter level 2"
Enter the password "viexpert".
6. "Reset all parameters"
Parameter levels
Parameter levels
5863679
Parameter