16
Example: Conversion to 100 °C
1.
2.
95
110120
°C
3.
Fig. 3
Adjusting the temperature controller (if required)
The temperature controller is supplied with a factory
setting of 95 °C.
!
Please note
Excessive DHW temperatures can damage the
DHW cylinder.
If the system is operated in conjunction with a
DHW cylinder, ensure that the maximum permis-
sible water temperature is not exceeded. If nec-
essary, install suitable safety equipment.
Example: Conversion to 100 °C
1.
3.
A
2.
Fig. 4
A
Tab for adjustment 75 to 100 °C
1.
Remove rotary selector "
R
".
2.
Using a pair of pointed pliers, break tab
A
identi-
fied in the illustration out of the stop dial.
3.
Fit rotary selector "
R
" so that the marking lies in
the centre of the selected range. Turn rotary selec-
tor "
R
" fully clockwise.
Installation sequence
Adjusting the high limit safety cut-out (if…
(cont.)