05 Burner curve
!
Display
Value
Explanations
Note
Factory setting, according to coding card
The burner curve varies depending on the type of
burner.
The burner curve shows the burner output (in %) in re-
lation to the opening angle of the butterfly valve (in
%).
See chapter "Matching the control unit to the modulat-
ing burner".
Linear burner curve
05:0
% of rated output at 1/3 of the modulation
range
05:1 to
05:99
06 Maximum boiler water temperature limit
!
Display
Value
Explanations
See chapter "Function description"
Note
■
Factory setting, according to coding card
■
Observe the temperature controller settings.
... °C
06:20 to
06:127
08 Maximum burner output in kW
!
Display
Value
Explanations
Note
Factory settings, according to coding card
... kW
08:0 to
08:199
1 step
≙
1 kW
09 Maximum burner output in 100 kW
!
Display
Value
Explanations
Note
Factory settings, according to coding card
... kW
09:0 to
09:199
1 step
≙
100 kW
Parameter
Boiler
(cont.)
5863679