A1
Circulation pump
A2
Circulation pump
fÖ
Power supply
fÖ
A Power supply for additional accessories
aVG
KM-BUS
Functions
One of the following circulation pumps can be connec-
ted to each of connections A1 and A2:
■
Heating circuit pump for heating circuit without mixer
■
Circulation pump for cylinder heating
■
DHW circulation pump
Connect DHW circulation pumps with standalone
functions directly to the 230 V
∼
supply.
Select the output functions via the parameters on the
boiler control unit.
Function assignment
Function
Parameter ("General" group)
Output A1
Output A2
DHW circulation pump
sK
31:0
Do not adjust
32:0 (factory setting)
Do not adjust
Heating circuit pump
sÖ
A1
31:1 (factory setting)
Do not adjust
32:1
Do not adjust
Circulation pump for cylinder heating
sA
31:2
32:2
Neutralising system, flue gas/water heat ex-
changer
sÖ
A1
31:3
32:3
Distribution pump
sL
31:4
Do not adjust
32:4
Do not adjust