80
12 Minimum collector temperature
Display
Value
Explanations
None
12:0
Minimum temperature limit disabled
10 °C
12:10
Minimum start temperature for solar circuit pump
10 °C
... °C
12:1 to
12:90
20 Extended control function
Display
Value
Explanations
None
20:0
No extended control function enabled
Additional function, increased DHW hy-
giene
20:1
Differential temperature control 2
20:2
Do not adjust in conjunction with Vitocell 100-W, type
CVUB-A
Differential temperature control 2 and auxil-
iary function for increased DHW hygiene
20:3
Do not adjust in conjunction with Vitocell 100-W, type
CVUB-A
Differential temperature control 2 for central
heating backup
20:4
Do not adjust in conjunction with Vitocell 100-W, type
CVUB-A
Thermostat function
20:5
Do not adjust in conjunction with Vitocell 100-W, type
CVUB-A
Thermostat function and auxiliary function
for increased DHW hygiene
20:6
Do not adjust in conjunction with Vitocell 100-W, type
CVUB-A
Solar heating via external heat exchanger
without additional temperature sensor
20:7
Solar heating via external heat exchanger
with additional temperature sensor
20:8
Do not adjust in conjunction with Vitocell 100-W, type
CVUB-A
Solar heating of 2 DHW cylinders
20:9
Do not adjust in conjunction with Vitocell 100-W, type
CVUB-A
22 Start temperature differential for central heating backup
Display
Value
Explanations
Parameter "20:4" must be set.
8 K
22:8
... K
22:2 to
22:30
23 Stop temperature differential for central heating backup
Display
Value
Explanations
Parameter "20:4" must be set.
4 K
23:4
... K
23:1 to
23:29
Parameter
Solar
(cont.)
5863679
Parameter
Содержание Vitotronic 11 CC1E