62
43 Function, input DE2 at extension EA1
Display
Value
Explanations
Displayed only if parameter "40:1" has been set.
None
43:0
Operating program changeover
43:1
Do not adjust
External demand with set flow temperature
43:2
External blocking
43:3
External blocking with fault message
43:4
External fault message
43:5
Brief operation, DHW circulation pump
(pushbutton function)
43:6
Do not adjust
44 Function, input DE3 at extension EA1
Display
Value
Explanations
Displayed only if parameter "40:1" has been set.
None
44:0
Operating program changeover
44:1
Do not adjust
External demand with set flow temperature
44:2
External blocking
44:3
External blocking with fault message
44:4
External fault message
44:5
Brief operation, DHW circulation pump
(pushbutton function)
44:6
Do not adjust
45 EA1 extension demand
Display
Value
Explanations
Displayed only if parameter "40:1" has been set.
See chapter "Function description"
Temperature demand
45:0
Output demand
45:1
Output demand
45:2
46 Demand 0 to 10 V, EA1 extension
Display
Value
Explanations
Displayed only if parameter "40:1" has been set.
Temperature demand 10 to 100 °C
46:0
Temperature demand 30 to 120 °C
46:1
51 Sensor 17A
Display
Value
Explanations
Not installed
51:0
Available
51:1
Recognised automatically.
Parameter
General
(cont.)