CFDV Series Gas Fireplace
20306739
41
CHECK GAS PRESSURE and ELECTRICAL INSTALLATION – IPI
CHECK GAS PRESSURE – IPI
1. Check gas type. The gas supply must be the same as
stated on the appliance’s rating decal. If the gas supply
is different from the fireplace,
STOP!
Do not install the
appliance. Contact your dealer immediately.
2. To facilitate easier installation, an 18" (610 mm) flex line
with manual shut-off valve has been provided with this
appliance. Install and attach 1/2" gas line onto shut-off
valve.
3. After completing gas line connection, purge air from
gas line and test all gas joints from the gas meter to the
fireplace for leaks. Use a solution of 50/50 water and
soap solution or a gas sniffer.
4. To check gas pressures at valve, turn captured screw
counter clockwise 2 or 3 turns and then place tubing
to pressure gauge over test point. Turn unit to high.
Figure 74.
After taking pressure reading, be sure and
turn captured screw clockwise firmly to reseal. Do not
over torque. Check test points for gas leaks. Ensure
that master switch and cold climate switch are turned
off before energizing unit.
CAUTION
Label all wires before disconnecting when
servicing controls. Wiring errors can cause
improper and dangerous operation.
Figure 74 –
IPI Valve
FP3034
IPI gas valve
Pressure Inlet
Pilot Adjust-
ment Screw
Pressure
Outlet
Do NOT
use open flame to check for gas leaks.
WARNING
Electrical connections should only be performed by
a qualified, licensed electrician. Main power must
be off when connecting to main electrical power
supply or performing service. All wiring shall be
in compliance with all local, city and state codes.
The appliance, when installed, must be electrically
grounded in accordance with local codes or in the
absence of local codes, with the National Electrical
Code ANSI/NFPA 70 (latest edition) and Canadian
Electrical Code, CSA C22.1.
WARNING
Before energizing a unit with IPI control system,
ensure that the master switch and cold climate
switch are in the OFF position.
WARNING
ELECTRICAL WIRING
General
1. This fireplace is equipped with an IPI control valve which
operates on 6 volts. The 6 volt DC adapter plugs into
the fireplace junction box A/C power supply.
2. The IPI system can also be operated without A/C power.
The system can run on four (4) “AA” batteries using the
optional battery backup for approximately four (4) to six
(6) months under normal use.
Optional Accessories
This fireplace may be used with a wall switch, wall mounted
thermostat or IPI hand held remote control.