12
20307394
4" x 6
5
⁄
8
" SLP Termination Kit
1. Flat Ceiling Installation
• Remove one shield from box.
NOTE:
Cut previously installed batt insulation to make
room for the attic insulation shield.
• Wrap shield around pipe if pipe is already installed
in area to be insulated.
• Match the three holes in each side and fasten with
three screws to form a tube.
• One or more tabs may be folded outward on the
bottom of the shield to allow attachment to ceiling
firestop.
• Bend remaining tabs inward on bottom of shield
where it rests on the ceiling firestop to maintain
the air space between the pipe and shield. Set the
shield on the ceiling firestop.
• Bend all tabs inward 90° around the top of the
shield. These tabs must be used to prevent blow-in
insulation from getting between the shield and vent
pipe, and to maintain clearance.
2. Vaulted Ceiling Installation
• Remove one shield from box.
Note: Cut previously installed batt insulation to
make room for the attic insulation shield.
• Cut the attic insulation shield (if application is for
vaulted ceiling) using a laser-etched cut line, to fit
your ceiling pitch. Snip cut edge to create three
bend tabs.
• Wrap shield around pipe if pipe is already installed
in area to be insulated.
• Match the three holes in each side and fasten with
three screws to form a tube.
• One or more tabs may be folded outward on the
bottom of the shield to allow attachment to ceiling
firestop.
• Bend remaining tabs inward on bottom of shield
where it rests on the ceiling firestop to maintain
the air space between the pipe and shield. Set the
shield on the ceiling firestop.
• Bend all tabs inward 90° around the top of the
shield. These tabs must be used to prevent blow-in
insulation from getting between the shield and vent
pipe, and to maintain clearance.
Bend all tabs inward
90° to maintain
clearance and
prevent insulation
from falling inside
Insert 3
screws
Bend 4 tabs
inward 90°
to maintain
clearance
Figure 5 Attic Insulation Shield
Roof Support
1. Fasten the roof support to the roof sheathing using
2” wood screws provided.
Figure 6.
Ensure that the
termination pipe is centered and has a minimum of
1” clearance on all sides from combustible materials.
Figure 7
2. Slip the rigid pipe section into the roof support to the
required height and tighten the two clamping bolts
to secure pipe. Also, level pipe vertically (plumb)
and secure by tightening the leveling bolts. (Refer to
fireplace instructions for chimney minimum heights
and clearances.)
NOTE: The roof support must be installed as
shown. Weld stud location to top for ease of
installation.
KT1076
roof support
Roof Support
Clinch Stud
Figure 6 Roof Support
1” Min.
Clearance
1” Min.
Clearance
KT1080
roof support top view
2 x 4
Framing
Leveling
Bolts
Clamping Bolts
Outline for Hole Cut in Roof
(Roof Sheeting Not Shown)
Screw
Screws
Figure 7 Typical Roof Support (top view)