DVB Series Direct Vent Gas Fireplace
20306740
25
FIREPLACE INSTALLATION
W
ARNING
Only persons licensed to work with gas
piping may make the necessary gas
connections to this appliance.
CAUTION
A manual shutoff valve must be installed
upstream of the appliance. Union tee
and plugged 1/8” NPT pressure tapping
point should be installed upstream of the
appliance.
Figure 42
NOTE : The gas line connection may be made using
1/2" rigid tubing or an approved flex connector. Since
some municipalities have additional local codes it
is always best to consult your local authorities and
the current edition of the National Fuel Gas Code
ANSI.Z223.1, NFPA54. In Canada CSA-B149 (1 or 2)
Installation Code.
A listed manual shutoff valve must be installed upstream of
the appliance. Union tee and plugged 1/8" NPT pressure
tapping point should be installed upstream of the appli-
ance.
Figure 42
IMPORTANT:
Install main gas valve (equipment shutoff
valve) in an accessible location. The main gas valve is for
turning on or shutting off the gas to the fireplace.
Check your building codes for any special requirements for
locating equipment shutoff valve to fireplaces.
Apply pipe joint sealant lightly to male threads. This will
prevent excess sealant from going into pipe. Excess seal-
ant in pipe could result in clogged burner system valves.
We recommend that you install a sediment trap/drip leg in
supply line as shown in
Figure 42
. Locate sediment trap/
drip leg where it is within reach for cleaning. Install in piping
system between fuel supply and burner system. Locate
sediment trap/drip leg where trapped matter is not likely
to freeze. A sediment trap collects moisture and contami-
nants and keeps them from going into the burner system
gas controls. If sediment trap/drip leg is not installed or is
installed wrong, burner system may not run properly.
CAUTION
Use pipe joint sealant that is resistant to
liquid petroleum (LP) gas.
3" Minimum
FP1978
gas connection
Pipe Nipple
Cap
Figure 42 -
Gas Connection
Tee Joint
Approved Flexible
Gas Line
CSA Design-Certified Equipment Shutoff Valve
with 1/8" NPT Tap*
Sediment Trap/Drip Leg
Natural Gas
From Gas Meter
(4.5" w.c. to 10.5" w.c. Pressure)
Propane/LP
From External Regulator
(11" w.c. to 13" w.c. Pressure)