DVB Series Direct Vent Gas Fireplace
16
20306740
REAR WALL VENT APPLICATION
When installed as a rear vent unit this appliance may be
vented directly to a termination located on the rear wall
behind the appliance.
•
Only Vermont Castings Group venting components
are approved to be used in these applications (Refer
to ‘Venting Components’ listed for different installation
requirements).
•
The maximum horizontal distance between the rear of
the appliance (or end of the transition elbow in a cor-
ner application) and the outside face of the rear wall is
20” (508 mm).
Figure 15
•
Only one 45° elbow is allowed in these installations.
•
Minimum clearances between vent pipe and combus-
tible materials are as follows:
Top - 3” (76 mm)
- except at outside wall 1" (25 mm)
Sides - 1” (25 mm)
Bottom - 1” (25 mm)
REAR WALL VENT INSTALLATION - TWIST
LOCK PIPE
Step 1
Locate and cut the vent opening in the wall.
For combustible walls first frame in opening.
Figure 17
NOTE:
When using flex vent, the opening will have to be
measured according to the 1” (25 mm) rise in 24” (610
mm) vertical run.
Combustible Walls:
Cut a 95/8”H x 95/8” W (244 x 244
mm) hole through the exterior wall and frame as shown.
Figure 17
Noncombustible Walls:
Hole opening should be 71/2”
(191 mm) diameter.
Step 2
Secure firestop to the inside frame, center in the 95/8" x
95/8" vent opening.
VO584-100
Vent Opening
2/99 djt
Vent Opening for Combustible Walls
95/8”
(244 mm)
Min.
Fireplace Hearth
Framing Detail
Opening for Noncombustible Wall
71/2”
(190 mm)
Fireplace Hearth
FP2293
Figure 17 -
Locate vent opening on wall.
95/8”
(244 mm) Min.
Step 3
Measure the horizontal length requirement for the venting
including a 2” (51 mm) overlap, i.e. from the elbow to the
outside wall face plus 2” (51 mm).
Figure 16
Step 4
Install the 4” (102 mm) vent to the appliance collar and
secure with 3 sheet metal screws. Install the 7” (178 mm)
vent pipe to the appliance collar and secure with 3 sheet
metal screws. It is not necessary to seal this connection.
If a 45° elbow is being used attach the elbow to the appli-
ance in the same manner then attach the venting to the
elbow.
It is critical that there is no downward slope
away from the appliance when connecting
the vent or elbow.
Step 5
Guide the venting through the vent hole as you place the
appliance in its installed position. Guide the 4” (102 mm)
and 7” (178 mm) collar of the vent termination into the
outer ends of the venting. Do not force the termination. If
the vent pipes do not align with the termination, remove
and realign the venting at the appliance flue collars.
Fig-
ure 18
. Attach the termination to the wall as outlined in the
instruction sheet supplied with the termination.
FP1188
rear wall install
20”
(508 mm)
Max.
20”
(508 mm)
Max.
Rear Vent Top
View
Figure 16 -
Rear Vent Appliaction, No Elbows
FP1188
VENTING INSTALLATION
For models purchased after 4/16/15, please see addendum.