5
20307394
4" x 6
5
⁄
8
" SLP Termination Kit
Secure the Vent Sections
Vertical sections of SLP pipe must be supported every 8 ft.
The SLP firestop includes tabs that may be used to secure
vertical sections.
The vent support or plumber’s strap (spaced 120° apart)
may be used to secure the vertical sections of pipe (see
Figure 5).
Horizontal sections of vent must be supported every 5 ft
with a vent support or plumber’s strap (see Figure 7).
Disassemble Vent Sections
To disassemble any two pieces of pipe, rotate either section
(Figure 8), so that the seams on both pipe sections are
aligned (Figure 9). They can then be carefully pulled apart.
Figure 6 - Securing Vertical Pipe Sections
Figure 7 - Securing Horizontal Pipe Sections
Figure 8 - Rotate Seams for Disassembly
WARNING
Risk of Fire/Explosion/Asphyxiation! Improper support
may allow vent to sag and separate. Use vent run
supports and connect vent sections per installation
instructions. DO NOT allow vent to sag below connection
point to appliance.
Figure 9 - Align and Disassemble Vent Sections