DVB Series Direct Vent Gas Fireplace
20
20306740
Step 7
Guide the vent terminations 4” and 7” collard into their
respective vent pipes. Double check that the vent pipes
overlap the collars by 2” (51 mm). Secure the termina-
tion to the wall with screws provided and caulk around the
wall plate to weatherproof. As an alternative to screwing
the termination directly to the wall, you may also use ex-
panding plugs or an approved exterior construction ad-
hesive. You may also attach the termination with screws
through the inner body into the 4” vent pipe, however for
this method, you must extend the 4” pipe approximately
6” (152 mm) beyond the outer face of the wall.
Support horizontal pipes every 36” (914
mm) with metal pipe straps.
VERTICAL SIDEWALL INSTALLATION -
FLEX VENT PIPE
NOTE:
The 40” (1016 mm) flex vent is used for 90° off the
top of the unit then out the back wall.
Follow Step 1 and 2 on
Page 19
.
Step 3
Install the four (4) spacer springs on the 4” flex vent pipe.
When installing the spacer springs around the 4” pipe,
stretch the spring to approximately 15” (381 mm), wrap
the spring around the pipe and interlock the ends of the
spacer spring approximately 2” (51 mm). Measure 63/4”
(172 mm) from the end of the pipe. Place the next spring
5” (127 mm) from the previously installed spring. Place
the next spring 6” (152 mm) from the last spring. Finally
place the last spring 12” (305 mm) from the last spring
installed.
Figure 30
Step 4
Install the 4” (102 mm) flex vent pipe to the appliance col-
lar as described on
Page 14
. Secure the end with the first
spring 63/4” (172 mm) from the flex pipe end to the unit.
Step 5
Slide the 7” (178 mm) flex vent pipe over the 4” flex vent
pipe and secure the 7” collar as described on
Page 13
.
Step 6
Bend the flex pipe horizontal so the bottom of the horizon-
tal pipe measure 61/2” (165 mm) from the top of the unit
immediately after the 90° formation.
Figure 31.
Be sure to
follow the 1/2” (13 mm) rise in a 12” (305 mm) horizontal
run rule.
Step 7
Install the 4” flex then 7” flex to the termination.
12"
(305mm)
6"
(152mm)
5"
(127mm)
6
³⁄₄
"
(172mm)
FP1474
spacer springs
4/04 djt
4” Flex Vent Pipe
Spacer Spring
FP1474
Figure 30 -
Install Spacer Springs
6
¹⁄₂
" (165mm)
FP1475
flex 90 bend
4/04 djt
Figure 31 -
Bend flex vent at 90° so horizontal portion is
6
1
⁄
2
” (165 mm) off top of unit
FP1475
VENTING INSTALLATION
For models purchased after 4/16/15, please see addendum.