![VERDER CARBOLITE GERO 3016 Скачать руководство пользователя страница 32](http://html.mh-extra.com/html/verder/carbolite-gero-3016/carbolite-gero-3016_installation-operation-and-maintenance-instructions_1003585032.webp)
TGT.sp
Target Setpoint
Used to adjust the setpoint temperature.
Note:
Also adjustable at Operator Level 3.
w.sp
Working
Setpoint
Displays the current working setpoint.
w.out
Working Output
Displays the current power output in %.
AtuN
Sublist:
Tune
Autotune Enable
Used to enable or disable an autotune.
l
On
- Autotune is enabled
l
Off
- Autotune is disabled
Note:
Also adjustable at Operator Level 3.
T.HI
Autotune
Maximum
Output
Used to set a maximum output limit during tuning.
The default value is
100
.
Note:
Also adjustable at Operator Level 3.
T.LO
Autotune
Minimum Output
Used to set a minimum output limit during tuning.
The default value is
-100
.
Note:
Also adjustable at Operator Level 3.
T.STAT
Autotune Status
Displays the current status of the autotune.
l
Off
- Autotune is unavailable.
l
Rdy
- The controller is ready to run an autotune
l
triG
- An autotune has been triggered to run, but is
waiting for another process to complete before run-
ning.
l
Run
- The autotune function is running.
l
donE
- The autotune completed successfully and tun-
eset parameters have been updated.
l
Abor
- The autotune has been aborted.
l
tOut
- If the autotune sequence exceeds two hours in
duration, it will timeout and be aborted.
l
OFLw
- A buffer overflow occurred while collecting pro-
cessing data. Contact Carbolite Gero Service for sup-
port.
STAGE
Stage of
Autotune
l
IdLe
- Not autotuning.
l
moni
- The process is being monitored. This stage lasts
one minute and the setpoint can be adjusted during this
time.
l
Init
- An initial oscillation is being established.
l
Hi
- Maximum output applied.