Control Connections
CG Drives & Automation, 01-5326-01r3b
4.2
Terminal connections
The terminal strip for connecting the control signals is
accessible after opening the front panel.
The table describes the default functions for the signals. The
inputs and outputs are programmable for other functions as
described in chapter 11. page 73. For signal specifications
refer to chapter 14. page 213.
NOTE: The maximum total combined current for outputs
11, 20 and 21 is 100mA.
NOTE: It is possible to use external 24V DC if connection
to Common (15).
Table 17
Control signals
Terminal
Name
Function (Default)
Outputs
1
+10 V
+10 VDC supply voltage
6
-10 V
-10 VDC supply voltage
7
Common
Signal ground
11
+24 V
+24 VDC supply voltage
12
Common
Signal ground
15
Common
Signal ground
Digital inputs
8
DigIn 1
RunL (reverse)
9
DigIn 2
RunR (forward)
10
DigIn 3
Off
16
DigIn 4
Off
17
DigIn 5
Off
18
DigIn 6
Off
19
DigIn 7
Off
22
DigIn 8
RESET
Digital outputs
20
DigOut 1
Ready
21
DigOut 2
Brake
Analogue inputs
2
AnIn 1
Process Ref
3
AnIn 2
Off
4
AnIn 3
Off
5
AnIn 4
Off
Analogue outputs
13
AnOut 1
Min speed to max speed
14
AnOut 2
0 to max torque
Relay outputs
31
N/C 1
Relay 1 output
Trip, active when the AC drive is
in a TRIP condition.
32
COM 1
33
N/O 1
41
N/C 2
Relay 2 output
Run, active when the AC drive is
started.
42
COM 2
43
N/O 2
51
COM 3
Relay 3 output
Off
52
N/O 3
NOTE: N/C is opened when the relay is active and N/O is
closed when the relay is active.
NOTE! Using potentiometer for reference signal to
Analogue input: Possible potentiometer value in range
of 1 k
Ƙ
to 10 k
Ƙ
(¼ Watt) linear, where we advice to
use a linear 1 k
Ƙ
/ ¼ W type potentiometer for best
control linearity.
WARNING!
The relay terminals 31-52 are single isolated.
Do NOT mix SELV voltage with e.g. 230 VAC
on these terminals. A solution when dealing
with mixed SELV/system voltage signals is to
install an additional I/O board option ( see
chapter 13.6 page 208) and connect all SELV
voltage signals to the relay terminals of this
option board while connecting all 230VAC
signals to the power board relay terminals 31
- 52.
Table 17
Control signals
Terminal
Name
Function (Default)
9(0R'ULYH 96, 9(0 U
Содержание VEMoDRIVE VSI 2.0 HD
Страница 1: ...Frequency converter VEMoDRIVE VSI 2 0 HD Instruction manual 01 5326 01 04 2018...
Страница 2: ......
Страница 4: ......
Страница 40: ...38 Installation CG Drives Automation 01 5326 01r3b 9 0R ULYH 96 9 0 U...
Страница 52: ...50 Getting Started CG Drives Automation 01 5326 01r3b 9 0R ULYH 96 9 0 U...
Страница 64: ...62 EMC and standards CG Drives Automation 01 5326 01r3b 9 0R ULYH 96 9 0 U...
Страница 142: ...140 Functional Description CG Drives Automation 01 5326 01r3b 9 0R ULYH 96 9 0 U...
Страница 198: ...196 CG Drives Automation 01 5326 01r3b 9 0R ULYH 96 9 0 U...
Страница 206: ...204 Troubleshooting Diagnoses and Maintenance CG Drives Automation 01 5326 01r3b 9 0R ULYH 96 9 0 U...
Страница 232: ...230 Technical Data CG Drives Automation 01 5326 01r3b 9 0R ULYH 96 9 0 U...
Страница 238: ...236 Menu List CG Drives Automation 01 5326 01r3b 9 0R ULYH 96 9 0 U...
Страница 243: ...241 9 0R ULYH 96 9 0 U...