142
CG Drives & Automation, 01-5326-01r3b
Load Type [415]
In this menu you select monitor type according to the load
characteristic of your application. By selecting the required
monitor type, the overload and underload alarm function
can be optimized according to the load characteristic.
When the application has a constant load over the whole
speed range, i.e. extruder or screw compressor, the load type
can be set to basic. This type uses a single value as a reference
for the nominal load. This value is used for the complete
speed range of the AC drive. The value can be set or
automatically measured. See Autoset Alarm [41A] and
“Normal Load [41B]” about setting the nominal load
reference.
The load curve mode uses an interpolated curve with 9 load
values at 8 equal speed intervals. This curve is populated by
a test run with a real load. This can be used with any smooth
load curve including constant load.
Fig. 106
Communication information
Max Alarm [416]
Max Alarm Margin [4161]
With load type Basic, [415], used the Max Alarm Margin
sets the band above the “Normal Load [41B]” menu that
does not generate an alarm. With load type Load Curve
[415], used the Max Alarm Margin sets the band above the
Load Curve [41C], that does not generate an alarm. The
Max Alarm Margin is a percentage of nominal motor
torque.
Communication information
Max Alarm delay [4162]
When the load level without interruption exceeds the alarm
level longer than set “Max Alarm delay” time, an alarm is
activated.
Communication information
Max Pre Alarm [417]
Max Pre AlarmMargin [4171]
With load type Basic [415], used the Max Pre-Alarm Margin
sets the band above the Normal Load, [41B], menu that
does not generate a pre-alarm. With load type Load Curve,
[415], used the Max Pre-Alarm Margin sets the band above
the Load Curve, [41C], that does not generate a pre-alarm.
Default:
Basic
Basic
0
Uses a fixed maximum and minimum load
level over the full speed range. Can be used
in situations where the torque is
independent of the speed.
Load
Curve
1
Uses the measured actual load
characteristic of the process over the speed
range.
Modbus Instance no/DeviceNet no:
43325
Profibus slot/index
169/229
EtherCAT index (hex)
4cfd
Profinet IO index
19709
Fieldbus format
UInt
Modbus format
UInt
Basic
Load curve
Load
Speed
Max Alarm
Min Alarm
415 Load Type
Stp
Basic
Default:
15%
Range:
0–400%
Modbus Instance no/DeviceNet no:
43326
Profibus slot/index
169/230
EtherCAT index (hex)
4cfe
Profinet IO index
19710
Fieldbus format
Long, 1=1%
Modbus format
Eint
Default:
0.1 s
Range:
0-90 s
Modbus Instance no/DeviceNet no:
43330
Profibus slot/index
169/234
EtherCAT index (hex)
4d02
Profinet IO index
19714
Fieldbus format
Long, 1=0.1 s
Modbus format
EInt
4161 MaxAlarmMar
Stp
15%
4162 MaxAlarmDel
Stp
0.1s
9(0R'ULYH 96, 9(0 U
Содержание VEMoDRIVE VSI 2.0 HD
Страница 1: ...Frequency converter VEMoDRIVE VSI 2 0 HD Instruction manual 01 5326 01 04 2018...
Страница 2: ......
Страница 4: ......
Страница 40: ...38 Installation CG Drives Automation 01 5326 01r3b 9 0R ULYH 96 9 0 U...
Страница 52: ...50 Getting Started CG Drives Automation 01 5326 01r3b 9 0R ULYH 96 9 0 U...
Страница 64: ...62 EMC and standards CG Drives Automation 01 5326 01r3b 9 0R ULYH 96 9 0 U...
Страница 142: ...140 Functional Description CG Drives Automation 01 5326 01r3b 9 0R ULYH 96 9 0 U...
Страница 198: ...196 CG Drives Automation 01 5326 01r3b 9 0R ULYH 96 9 0 U...
Страница 206: ...204 Troubleshooting Diagnoses and Maintenance CG Drives Automation 01 5326 01r3b 9 0R ULYH 96 9 0 U...
Страница 232: ...230 Technical Data CG Drives Automation 01 5326 01r3b 9 0R ULYH 96 9 0 U...
Страница 238: ...236 Menu List CG Drives Automation 01 5326 01r3b 9 0R ULYH 96 9 0 U...
Страница 243: ...241 9 0R ULYH 96 9 0 U...