130
Functional Description
CG Drives & Automation, 01-5326-01r3b
11.3.10
Pump/Fan Control [390]
The
Q
ump
D
ontrol functions are in menu [390]. The
function is used to control a number of drives (pumps, fans,
etc.) of which one is always driven by the AC drive.
Pump enable [391]
This function will enable the pump control to set all relevant
pump control functions.
Communication information
Number of Drives [392]
Sets the total number of drives which are used, including the
Master AC drive. The setting here depends on the parameter
“Select Drive [393]”. After the number of drives is chosen it
is important to set the relays for the pump control. If the
digital inputs are also used for status feedback, these must be
set for the pump control according to; Pump 1 OK– Pump6
OK in menu
[520].
Communication information
Select Drive [393]
Sets the main operation of the pump system. 'Sequence' and
'Runtime' are Fixed MASTER operation. 'All' means
Alternating MASTER operation.
Communication information
Default:
Off
Off
0
Pump control is switched off.
On
1
Pump control is on:
- Pump control parameters [392] to [39G]
appear and are activated according to
default settings.
- View functions [39H] to [39M] are added
in the menu structure.
Modbus Instance no/DeviceNet no:
43161
Profibus slot/index
169/65
EtherCAT index (hex)
4c59
Profinet IO index
19545
Fieldbus format
UInt
Modbus format
UInt
Default:
2
1-3
Number of drives if I/O Board is not used.
1-6
Number of drives if 'Alternating MASTER' is
used, see Select Drive [393]. (I/O Board is
used.)
1-7
Number of drives if 'Fixed MASTER' is used,
see Select Drive [393].
(I/O Board is used.)
NOTE: Used relays must be defined as Slave Pump or
Master Pump. Used digital inputs must be defined as
Pump Feedback.
391 Pump enable
Stp
Off
392 No of Drives
Stp
2
Modbus Instance no/DeviceNet no:
43162
Profibus slot/index
169/66
EtherCAT index (hex)
4c5a
Fieldbus format
UInt
Modbus format
UInt
Default:
Sequence
Sequence 0
Fixed MASTER operation:
- The additional drives will be selected in
sequence, i.e. first pump 1 then pump 2
etc.
- A maximum of 7 drives can be used.
Run Time 1
Fixed MASTER operation:
- The additional drives will be selected
depending on the Run Time. So the drive
with the lowest Run Time will be selected
first. The Run Time is monitored in menus
[39H] to [39M] in sequence. For each drive
the Run Time can be reset.
- When drives are stopped, the drive with
the longest Run Time will be stopped first.
- Maximum 7 drives can be used.
All
2
Alternating MASTER operation:
- When the drive is powered up, one drive is
selected as the Master drive. The selection
criteria depends on the Change Condition
[394]. The drive will be selected according
to the Run Time. So the drive with the
lowest Run Time will be selected first. The
Run Time is monitored in menus [39H] to
[39M] in sequence. For each drive the Run
Time can be reset.
- A maximum of 6 drives can be used.
Modbus Instance no/DeviceNet no:
43163
Profibus slot/index
169/67
EtherCAT index (hex)
4c5b
Profinet IO index
19547
Fieldbus format
UInt, 1=1
Modbus format
UInt
NOTE: This menu will NOT be active if only one drive is
selected.
393 Select Drive
Stp
Sequence
9(0R'ULYH 96, 9(0 U
Содержание VEMoDRIVE VSI 2.0 HD
Страница 1: ...Frequency converter VEMoDRIVE VSI 2 0 HD Instruction manual 01 5326 01 04 2018...
Страница 2: ......
Страница 4: ......
Страница 40: ...38 Installation CG Drives Automation 01 5326 01r3b 9 0R ULYH 96 9 0 U...
Страница 52: ...50 Getting Started CG Drives Automation 01 5326 01r3b 9 0R ULYH 96 9 0 U...
Страница 64: ...62 EMC and standards CG Drives Automation 01 5326 01r3b 9 0R ULYH 96 9 0 U...
Страница 142: ...140 Functional Description CG Drives Automation 01 5326 01r3b 9 0R ULYH 96 9 0 U...
Страница 198: ...196 CG Drives Automation 01 5326 01r3b 9 0R ULYH 96 9 0 U...
Страница 206: ...204 Troubleshooting Diagnoses and Maintenance CG Drives Automation 01 5326 01r3b 9 0R ULYH 96 9 0 U...
Страница 232: ...230 Technical Data CG Drives Automation 01 5326 01r3b 9 0R ULYH 96 9 0 U...
Страница 238: ...236 Menu List CG Drives Automation 01 5326 01r3b 9 0R ULYH 96 9 0 U...
Страница 243: ...241 9 0R ULYH 96 9 0 U...