Functional Description
CG Drives & Automation, 01-5326-01r3b
Flux Optimization [354]
Flux Optimization reduces the energy consumption and the
motor noise, at low or no load conditions.
Flux Optimization automatically decreases the V/Hz ratio,
depending on the actual load of the motor when the process
is in a steady situation. Fig. 93 shows the area within which
the Flux Optimization is active.
Communication information
Fig. 93 Flux Optimizing
Maximum power [355]
Sets maximum power. Can be used for limiting motor
power in field weakening operation. This function operates
as an upper power limit and internally limits the parameter
“Max Torque [351]” according to :
Tlimit = Plimit[%] / (Actual Speed / Sync Speed)
Communication information
NOTE: A too high level of IxR Compensation could cause
motor saturation. This can cause a “Power Fault” trip.
The effect of IxR Compensation is stronger with higher
power motors.
NOTE: The motor may be overheated at low speed.
Therefore it is important that the Motor I
2
t Current [232]
is set correctly.
Default:
Off
Off
0
Function disabled
On
1
Function enabled
Modbus Instance no/DeviceNet no:
43144
Profibus slot/index
169/48
EtherCAT index (hex)
4c48
Profinet IO index
19528
Fieldbus format
UInt
Modbus format
UInt
NOTE: Flux optimization works best at stable situations
in slow changing processes.
354 Flux optim
Stp
Off
50
Hz
f
%
U
100
Flux optimizing
area
Default:
Off
Off
0
Off. No power limit
1 - 400
1 - 400
1 - 400% of motor nominal power
NOTE: The maximum possible setting for parameter
[355] is limited by I
NOM
/I
MOT
x 120%, but not higher
than 400%.
Modbus Instance no/DeviceNet no:
43145
Profibus slot/index
169/49
EtherCAT index (hex)
4c49
Profinet IO index
19529
Fieldbus format
Long, 1=1%
Modbus format
EInt
355 Max Power
Stp
Off
9(0R'ULYH 96, 9(0 U
Содержание VEMoDRIVE VSI 2.0 HD
Страница 1: ...Frequency converter VEMoDRIVE VSI 2 0 HD Instruction manual 01 5326 01 04 2018...
Страница 2: ......
Страница 4: ......
Страница 40: ...38 Installation CG Drives Automation 01 5326 01r3b 9 0R ULYH 96 9 0 U...
Страница 52: ...50 Getting Started CG Drives Automation 01 5326 01r3b 9 0R ULYH 96 9 0 U...
Страница 64: ...62 EMC and standards CG Drives Automation 01 5326 01r3b 9 0R ULYH 96 9 0 U...
Страница 142: ...140 Functional Description CG Drives Automation 01 5326 01r3b 9 0R ULYH 96 9 0 U...
Страница 198: ...196 CG Drives Automation 01 5326 01r3b 9 0R ULYH 96 9 0 U...
Страница 206: ...204 Troubleshooting Diagnoses and Maintenance CG Drives Automation 01 5326 01r3b 9 0R ULYH 96 9 0 U...
Страница 232: ...230 Technical Data CG Drives Automation 01 5326 01r3b 9 0R ULYH 96 9 0 U...
Страница 238: ...236 Menu List CG Drives Automation 01 5326 01r3b 9 0R ULYH 96 9 0 U...
Страница 243: ...241 9 0R ULYH 96 9 0 U...