![VEM VEMoDRIVE VSI 2.0 HD Скачать руководство пользователя страница 180](http://html1.mh-extra.com/html/vem/vemodrive-vsi-2-0-hd/vemodrive-vsi-2-0-hd_instruction-manual_3985886180.webp)
178
CG Drives & Automation, 01-5326-01r3b
Z Comp 2 [633]
Selects the second comparator for the logic Z function.
Communication information
Z Operator 2 [634]
Selects the second operator for the logic Z function.
Communication information
Z Comp 3 [635]
Selects the third comparator for the logic Z function.
Communication information
11.6.4 Timer1 [640]
The Timer functions can be used as a delay timer or as an
interval with separate On and Off times (alternate mode). In
delay mode, the output signal T1Q becomes high if the set
delay time is expired. See Fig. 122.
Fig. 122
In alternate mode, the output signal T1Q will switch
automatically from high to low etc. according to the set
interval times “Timer1 T1” and “Timer 1 T2”. See Fig. 123.
The output signal can be programmed to the digital or relay
outputs used in logic functions [620] and [630], or as a
virtual connection source [560].
Fig. 123
Default:
!A2
Selection:
Same as menu [621]
Modbus Instance no/DeviceNet no:
43423
Profibus slot/index
170/72
EtherCAT index (hex)
4d5f
Profinet IO index
19807
Fieldbus format
UInt
Modbus format
UInt
Default:
&
Selection:
Same as menu [624]
Modbus Instance no/DeviceNet no:
43424
Profibus slot/index
170/73
EtherCAT index (hex)
4d60
Profinet IO index
19808
Fieldbus format
UInt
Modbus format
UInt
Default:
CD1
Selection:
Same as menu [621]
Modbus Instance no/DeviceNet no:
43425
Profibus slot/index
170/74
EtherCAT index (hex)
4d61
Profinet IO index
19809
Fieldbus format
UInt
Modbus format
UInt
633 Z Comp 2
Stp
!A2
634 Z Operator 2
Stp
&
635 Z Comp 3
Stp
CD1
NOTE: The actual timers are common for all parameter
sets. If the actual set is changed, the timer functionality
[641] to [645] will change according set settings but the
timer value will stay unchanged. So initialization of the
timer might differ for a set change compared to normal
triggering of a timer.
Timer1 Trig
T1Q
Timer1 delay
Timer1 T2 Timer1 T1
Timer1 Trig
T1Q
Timer1 T2 Timer1 T1
9(0R'ULYH 96, 9(0 U
Содержание VEMoDRIVE VSI 2.0 HD
Страница 1: ...Frequency converter VEMoDRIVE VSI 2 0 HD Instruction manual 01 5326 01 04 2018...
Страница 2: ......
Страница 4: ......
Страница 40: ...38 Installation CG Drives Automation 01 5326 01r3b 9 0R ULYH 96 9 0 U...
Страница 52: ...50 Getting Started CG Drives Automation 01 5326 01r3b 9 0R ULYH 96 9 0 U...
Страница 64: ...62 EMC and standards CG Drives Automation 01 5326 01r3b 9 0R ULYH 96 9 0 U...
Страница 142: ...140 Functional Description CG Drives Automation 01 5326 01r3b 9 0R ULYH 96 9 0 U...
Страница 198: ...196 CG Drives Automation 01 5326 01r3b 9 0R ULYH 96 9 0 U...
Страница 206: ...204 Troubleshooting Diagnoses and Maintenance CG Drives Automation 01 5326 01r3b 9 0R ULYH 96 9 0 U...
Страница 232: ...230 Technical Data CG Drives Automation 01 5326 01r3b 9 0R ULYH 96 9 0 U...
Страница 238: ...236 Menu List CG Drives Automation 01 5326 01r3b 9 0R ULYH 96 9 0 U...
Страница 243: ...241 9 0R ULYH 96 9 0 U...