Analogue Comparator 1,
Level High [6112]
Sets the analogue comparator high level, with range
according to the selected value in menu [6111].
Min/Max setting range for menu [6112]
Communication information
No.
Description
1
The reference signal passes the Level LO value from
below (positive edge), the comparator CA1 output stays
low, mode=RUN.
2
The reference signal passes the Level HI value from
below (positive edge), the comparator CA1 output is set
high, mode=RUN.
3
The reference signal passes the threshold level of 4 mA,
the motor speed will now follow the reference signal.
T
During this period the motor speed will follow the
reference signal.
4
The reference signal reaches the threshold level, motor
speed is 0 rpm, mode = RUN.
5
The reference signal passes the Level HI value from
above (negative edge), the comparator CA1 output stays
high, mode =RUN.
6
The reference signal passes the Level LO value from
above (negative edge), the comparator CA1
output=STOP.
1 2
3
4
5
6
20 mA
4 mA
3.2 mA
2.4 mA
CA1 Level HI = 16%
CA1 Level LO = 12%
Max speed
Reference signal AnIn1
CA1
Mode
RUN
STOP
T
t
t
t
Default:
300 rpm
Range:
See min/max in table below.
Mode
Min
Max
Decimals
Process Val
Set by Process settings
[321] and [322]
3
Speed, rpm
0
Max speed
0
Torque, %
0
Max torque
0
Shaft Power, kW
0
Motor P
n
x4
0
El Power, kW
0
Motor P
n
x4
0
Current, A
0
Motor I
n
x4
1
Output volt, V
0
1000
1
Frequency, Hz
0
400
1
DC voltage, V
0
1250
1
Heatsink temp,
°
C
0
100
1
PT 100_1_2_3,
°
C
-100
300
1
Energy, kWh
0
1000000
0
Run time, h
0
65535
0
Mains time, h
0
65535
0
AnIn 1-4%
0
100
0
Process Ref
Set by Process settings
[321] and [322]
3
Process Err
Set by Process settings
[321] and [322]
3
NOTE: If Bipolar selected [6115] then Min value is equal
to -Max in the table.
Modbus Instance no/DeviceNet no:
43402
Profibus slot/index
170/51
EtherCAT index (hex)
4d4a
Profinet IO index
19786
Fieldbus format
Long,
1=1 W, 0.1 A, 0.1 V,
0.1 Hz, 0.1
°
C, 1 kWh, 1H,
1%, 1 rpm or 0.001 via
process value
Modbus format
EInt
6112 CA1 Level HI
Stp
300rpm
9(0R'ULYH 96, 9(0 U
Содержание VEMoDRIVE VSI 2.0 HD
Страница 1: ...Frequency converter VEMoDRIVE VSI 2 0 HD Instruction manual 01 5326 01 04 2018...
Страница 2: ......
Страница 4: ......
Страница 40: ...38 Installation CG Drives Automation 01 5326 01r3b 9 0R ULYH 96 9 0 U...
Страница 52: ...50 Getting Started CG Drives Automation 01 5326 01r3b 9 0R ULYH 96 9 0 U...
Страница 64: ...62 EMC and standards CG Drives Automation 01 5326 01r3b 9 0R ULYH 96 9 0 U...
Страница 142: ...140 Functional Description CG Drives Automation 01 5326 01r3b 9 0R ULYH 96 9 0 U...
Страница 198: ...196 CG Drives Automation 01 5326 01r3b 9 0R ULYH 96 9 0 U...
Страница 206: ...204 Troubleshooting Diagnoses and Maintenance CG Drives Automation 01 5326 01r3b 9 0R ULYH 96 9 0 U...
Страница 232: ...230 Technical Data CG Drives Automation 01 5326 01r3b 9 0R ULYH 96 9 0 U...
Страница 238: ...236 Menu List CG Drives Automation 01 5326 01r3b 9 0R ULYH 96 9 0 U...
Страница 243: ...241 9 0R ULYH 96 9 0 U...