104
Functional Description
CG Drives & Automation, 01-5326-01r3b
DHCP [2655]
Communication information
Fieldbus Signals [266]
Defines modbus mapping for additional process values. For
further information, see the Fieldbus option manual.
FB Signal 1 - 16 [2661]-[266G]
Used to create a block of parameters which are read/written
via communication. 1 to 8 read + 1 to 8 write parameters
possible.
Communication information
FB Status [269]
Sub menus showing status of fieldbus parameters. Please see
the Fieldbus manual for detailed information.
11.3 Process and Application
Parameters [300]
These parameters are mainly adjusted to obtain optimum
process or machine performance.
The read-out, references and actual values depends on
selected process source, [321}:
11.3.1 Set/View Reference Value
[310]
View reference value
As default the menu [310] is in view operation. The value of
the active reference signal is displayed. The value is displayed
according to selected process source, [321] or the process
unit selected in menu [322].
Set reference value
If the function “Reference Control [214]” is set to
“Keyboard”, the reference value can be set in menu “Set/
View Ref [310]” or as a motor potentiometer with the + and
- keys (default) on the control panel. Selection is made with
parameter Keyboard Reference Mode in menu [369]. The
ramp times used when setting the reference value with
MotPot function selected in [369] are according to menus
“Acc MotPot [333]” and “Dec MotPot [334]”.
The ramp times used for the reference value when Normal
function is selected in menu [369], are according to “Acc
Time [331]” and “Dec Time [332]”.
Menu [310] displays on-line the actual reference value
according to the Mode Settings in Table 27
.
Default:
Off
Selection:
On/Off
Modbus Instance no/DeviceNet no:
42719
Profibus slot/index
167/133
EtherCAT index (hex)
4a9f
Profinet IO index
19103
Fieldbus format
UInt
Modbus format
UInt
Default:
0
Range:
0-65535
Modbus Instance no/DeviceNet no:
42801-42816
Profibus slot/index
167/215-167/230
EtherCAT index (hex)
4af1 - 4b00
Profinet IO index
19185 - 19200
Fieldbus format
UInt, 1=1
Modbus format
UInt
2655 DHCP
Stp
Off
2661 FB Signal 1
Stp
0
269 FB Status
Stp
Table 27
Selected process
source
Unit for reference and
actual value
Resolution
Speed
rpm
4 digits
Torque
%
3 digits
PT100
°
C
3 digits
Frequency
Hz
3 digits
Default:
0 rpm
Dependent on:
Process Source [321] and Process Unit
[322]
Speed mode
0 - max speed [343]
Torque mode
0 - max torque [351]
Other modes
Min according to menu [324] - max
according to menu [325]
310 Set/View ref
Stp
0rpm
9(0R'ULYH 96, 9(0 U
Содержание VEMoDRIVE VSI 2.0 HD
Страница 1: ...Frequency converter VEMoDRIVE VSI 2 0 HD Instruction manual 01 5326 01 04 2018...
Страница 2: ......
Страница 4: ......
Страница 40: ...38 Installation CG Drives Automation 01 5326 01r3b 9 0R ULYH 96 9 0 U...
Страница 52: ...50 Getting Started CG Drives Automation 01 5326 01r3b 9 0R ULYH 96 9 0 U...
Страница 64: ...62 EMC and standards CG Drives Automation 01 5326 01r3b 9 0R ULYH 96 9 0 U...
Страница 142: ...140 Functional Description CG Drives Automation 01 5326 01r3b 9 0R ULYH 96 9 0 U...
Страница 198: ...196 CG Drives Automation 01 5326 01r3b 9 0R ULYH 96 9 0 U...
Страница 206: ...204 Troubleshooting Diagnoses and Maintenance CG Drives Automation 01 5326 01r3b 9 0R ULYH 96 9 0 U...
Страница 232: ...230 Technical Data CG Drives Automation 01 5326 01r3b 9 0R ULYH 96 9 0 U...
Страница 238: ...236 Menu List CG Drives Automation 01 5326 01r3b 9 0R ULYH 96 9 0 U...
Страница 243: ...241 9 0R ULYH 96 9 0 U...