Chapter 8 Functional Parameter Table
ACH200 Series High Voltage Variable Frequency Speed Control System Operating Manual
104
8: Terminal selection
9: Active current component
(local)
FB.04
Feedback signal
filtering time
0.000s~6.000s
0.010s
●
△
0xB04
FB.05
Feedback signal
gain
0.00~10.00
1.00
●
△
0xB05
FB.06
Setting
and
feedback ranges
0.0~100.0
100.0
●
△
0xB06
FB.07
PID
Control
options
LED one digits: Feedback
characteristic selection
0: Positive characteristic
1: negative characteristic
LED ten digits, hundred
digits: reserved
LED
thousand
digits:
differential
adjustment
property
0: Differential for deviation
1: Differential for feedback
0100
●
△
0xB07
FB.08
PID preset output
0.0%~100.0%
100.0%
●
△
0xB08
FB.09
Preset
output
runtime
0.0s~6500.0s
0.0s
●
△
0xB09
FB.10
PID
control
deviation limit
0.0%~100.0%
0.0%
●
△
0xB0A
FB.11
Proportional gain
P1
0.000~4.000
0.100
●
△
0xB0B
FB.12
Integration time
I1
0.0s~600.0s
5.0s
●
△
0xB0C
FB.13
Differential gain
D 1
0.000s~6.000s
0.000s
●
△
0xB0D
FB.14
proportional gain
P2
0.000~4.000
0.500
●
△
0xB0E
FB.15
Points time I2
0.0s~600.0s
5.0s
●
△
0xB0F
FB.16
differential gain
D2
0.000s~6.000s
0.000s
●
△
0xB10
FB.17
PID parameter
switching
conditions
0: no switch
1: Switching using DI
terminals
2: Switching according to
deviation
0
●
△
0xB11
FB.18
Toggle Deviation
Low
0.0%~100.0%
20.0%
●
△
0xB12
FB.19
Toggle deviation
high value
0.0%~100.0%
80.0%
●
△
0xB13
FB.21
differential
limiting
0.0%~100.0%
5.0%
●
△
0xB15
FB.22
PID output upper
limit
0.0%~100.0%
2.0%
●
△
0xB16
FB.23
PID output lower
limit
-Fb.22~Fb.22
-2.0%
●
△
0xB17
FB.24
PID output
filtering time
0.000s~6.000s
0.000s
●
△
0xB18
FB.25
Feedback
disconnection
detection time
0.0s~120.0s
1.0s
●
△
0xB19