Chapter 7 Modbus Communication Protocol
ACH200 Series High Voltage Variable Frequency Speed Control System Operating Manual
72
status
R
Bit1
0:
Non-
accelerated
state
1:
Accelerated
state
Bit2
0:
Non-
deceleration
state
1:
Deceleration
status
Bit3
0: Positive
1: Reverse
Bit4
0: Trouble-
free
1: AC drive
failure
Bit5
0:
Slave
normal
1:
Faulty
slave
or
slave
in
emergency
stop
Bit6
0:
No
warning
1: AC drive
warning
Bit7
0: Power-up
not
completed
1: Power up
completed
AC drive fault code
0x3003or
0x2003
AC drive current fault code (see
fault code table)
)
R
Communication
given upper frequency
0x3004 or
0x2004
0~32000
Correspondence
0.00Hz~320.00Hz
W/R
Communication
torque setting
0x3005 or
0x2005
0~1000
Correspondence
0.0%~100.0%
W/R
Torque
control
forward maximum
frequency limit
0x3006 or
0x2006
0~1000
Correspondence
0.0%~100.0%
W/R
Torque
control
reverse maximum
frequency limit
0x3007 or
0x2007
0~1000
Correspondence
0.0%~100.0%
W/R
PID giving
0x3008 or
0x2008
0~1000
Correspondence
0.0%~100.0%
W/R
PID feedback
0x3009 or
0x2009
0~1000
Correspondence
0.0%~100.0%
W/R
Voltage
and
frequency separation
voltage value setting
0x300A or
0x200A
0~1000
Correspondence
0.0%~100.0%
W/R
Fault marker 1~16
0x300B or
0x200B
0~FFFF
;
bit0~bit15 Corresponding
faults 1~16
R
Fault marker 17~32
0x300Cor
0x200C
0~FFFF
;
bit0~bit15 Corresponding
faults 17~32
R
Fault marker 33~48
0x300D or
0x200D
0~FFFF
;
bit0~bit15 Corresponding
faults 33~48
R
Fault marker 49~64
0x300E or
0x200E
0~FFFF
;
bit0~bit14 Corresponding
faults 49~63
R
AC drive special
status
0x300F or
0x200F
Bit0
0:
Downtime
status
1: Operation
Status
R
Bit1
0:
Non-
accelerated
state
1:
Accelerated
state