Chapter 8 Functional Parameter Table
ACH200 Series High Voltage Variable Frequency Speed Control System Operating Manual
93
0: Same direction
1: opposite direction
LED hundred digits:
broken wire detection
0: off
1: on
LED thousand digits: Z
pulse correction
0: off
1: On
F5.31
Number of ABZ
encoder lines
1~10000
1024
〇
△
0x51F
F5.32
Broken
wire
detection time
0.100s~60.000s
0.500s
●
△
0x520
F5.33
Number of resolver
poles
2~128
2
〇
△
0x521
F5.34
Encoder
ratio
molecule
1~32767
1
〇
△
0x522
F5.35
Encoder
ratio
denominator
1~32767
1
〇
△
0x523
F5.36
Encoder
speed
measurement first
order filtering
0.0ms~100.0ms
1.0ms
●
△
0x524
F5.39
Open-loop
PG
feedback
display
switch selection
One
digits:
C-29PG
feedback display switch
0: Close PG feedback
display
1: Turn on the PG
feedback display
0000
●
△
0x527
8.1.7 F6 Motor Vector Control Group
Functio
n Code
Function
code
name
Setting value range and
definition
Factory
settings
Prop
erties
Address
F6.00
ASR (speed loop)
proportional gain 1
0.01~100.00
4.00
●
△
0x600
F6.01
ASR (speed loop)
integration time 1
0.000s~6.000s
0.500s
●
△
0x601
F6.02
ASR
filtering
time1
0.0ms~100.0ms
0.0ms
●
△
0x602
F6.03
ASR
switching
frequency1
0.00Hz~maximum
frequency
0.00Hz
●
△
0x603
F6.04
ASR (speed loop)
proportional gain 2
0.01~100.00
10.00
●
△
0x604
F6.05
ASR (speed loop)
integration time2
0.000s~6.000s
0.100s
●
△
0x605
F6.06
ASR
filtering
time2
0.0ms~100.0ms
0.0ms
●
△
0x606
F6.07
ASR
switching
frequency2
0.00Hz~maximum
frequency
0.00Hz
●
△
0x607
F6.08
Electric
torque
limiting
0.0%~400.0%
180.0%
●
△
0x608
F6.09
Power generation
torque limitation
0.0%~400.0%
180.0%
●
△
0x609