Chapter 8 Functional Parameter Table
ACH200 Series High Voltage Variable Frequency Speed Control System Operating Manual
96
selection
1 to 9: reserved;
10: square V/F curve;
11: custom V/F curve
;
F8.01
Self-setting
voltage V1
0.0%~100.0%
3.0%
〇
△
0x801
F8.02
Self-setting
frequency F1
0.00Hz~Max Frequency
1.00Hz
〇
△
0x802
F8.03
Self-setting
voltage V2
0.0%~100.0%
28.0%
〇
△
0x803
F8.04
Self-setting
frequency F2
0.00Hz~Max Frequency
10.00Hz
〇
△
0x804
F8.05
Self-setting
voltageV3
0.0%~100.0%
55.0%
〇
△
0x805
F8.06
Self-setting
frequencyF3
0.00Hz~Max Frequency
25.00Hz
〇
△
0x806
F8.07
Self-setting
voltageV4
0.0%~100.0%
78.0%
〇
△
0x807
F8.08
Self-setting
frequencyF4
0.00Hz~Max Frequency
37.50Hz
〇
△
0x808
F8.09
Self-setting
voltageV5
0.0%~100.0%
100.0%
〇
△
0x809
F8.10
Self-setting
frequencyF5
0.00Hz~Max Frequency
50.00Hz
〇
△
0x80A
F8.11
Output voltage
percentage
25.0%~120.0%
100.0%
〇
△
0x80B
F8.12
Torque boost
0.0%~30.0%
Model
determinat
ion
●
△
0x80C
F8.13
Torque boost cut-
off frequency
0.0%~100.0%
100.0%
●
△
0x80D
F8.14
Differential
compensation
gain
0.0%~200.0%
100.0%
●
△
0x80E
F8.15
Transition
compensation
limit
0.0%~300.0%
10.0%
●
△
0x80F
F8.16
Rotation
difference
compensation
filtering time
0.000s~6.000s
0.5000s
●
△
0x810
F8.17
Oscillation
rejection gain
0.0%~900.0%
100.0%
●
△
0x811
F8.18
Oscillation
rejection
filter
coefficient
1.0~100.0
1.0
●
△
0x812
F8.19
Automatic
energy
saving
control
0: Off
1: On
0
〇
△
0x813
F8.20
Energy
saving
step-down
frequency lower
limit
0.00Hz~50.00Hz
15.00Hz
〇
△
0x814
F8.21
Energy
saving
step-down
voltage
lower
limit
20.0%~100.0%
50.0%
〇
△
0x815