Chapter 8 Functional Parameter Table
ACH200 Series High Voltage Variable Frequency Speed Control System Operating Manual
109
LED
hundred
digits:
Extended
485-3
communication:
0: Write operation with
response
1: No response for write
operation
FD.11
Host
send
selection
LED one digits: first set of
transmit frames selected
0: invalid
1: Host run command
2: Host given frequency
3: Host output frequency
4: Host upper limit frequency
5: Host given torque
6: Host output torque
7: Torque control forward
speed limit
8: Torque control reverse
speed limit
9: Host PID giving
A: Host PID feedback
B: Reservation
C: Torque current component
LED ten digits: second group
of sending frame selection
Same as above
LED hundred digits: the third
group of sending frame
selection
Same as above
LED thousand digits: fourth
group of transmit frame
selection
Same as above
0C31
●
0xD0B
FD.12
CAN
communication
protocol
selection
0: CANopen slave
1: Veichi Custom Slave
2: Veichi Custom Master
FD.12
●
0xD0C
FD.13
CAN
communication
address
1~247
FD.13
●
0xD0D
FD.14
Communication
baud
rate
selection
0: 20kbps
1: 50 kbps
2:100kbps
3: 125kbps
4:250kbps
5: 500kbps
6: 1Mbps
FD.14
●
0xD0E
FD.15
Custom
cyclic
transmission
One digits, Ten digits,
Hundred digits and Thousand
FD.15
●