Chapter 8 Functional Parameter Table
ACH200 Series High Voltage Variable Frequency Speed Control System Operating Manual
92
F5.04
Motor rated speed
1rpm~65000rpm
Model
Setting
※
〇
△
0x504
F5.05
Motor rated voltage
1V~1500V
Model
Setting
※
〇
△
0x505
F5.07
Asynchronous
motor
no-load
current
0.1A~3000.0A
Model
Setting
※
〇
△
0x507
F5.08
Asynchronous
motor
stator
resistance
0.01%~50.00%
Model
Setting
※
〇
△
0x508
F5.09
Rotor resistance of
asynchronous
motors
0.01%~50.00%
Model
Setting
※
〇
△
0x509
F5.10
Asynchronous
motor stator leakage
inductance
0.01%~50.00%
Model
Setting
※
〇
△
0x50A
F5.11
Asynchronous
motor
stator
inductance
0.1%~2000.0%
Model
Setting
※
〇
△
0x50B
F5.12
Synchronous
machine
stator
resistance
0.01%~50.00%
Model
Setting
※
〇
△
0x50C
F5.13
Synchronizer D-axis
inductor
0.01%~200.00%
Model
Setting
※
〇
△
0x50D
F5.14
Synchronizer Q-axis
inductor
0.01%~200.00%
Model
Setting
※
〇
△
0x50E
F5.15
Synchronous
machine
counter-
electromotive force
0V~3500V
Model
Setting
※
〇
△
0x50F
F5.16
Synchronizer
encoder mounting
angle
0.0°~360.0°
Model
Setting
※
●
△
0x510
F5.20
Motor
parameter
self-tuning selection
0: No operation
1: Rotational self-learning
2: Static type self-learning
3: Stator resistance self-
learning
0
〇
△
0x514
F5.21
Synchronous motor
pole search function
LED one digits: closed-
loop vector
0: off 1: on
2: On at first power-up
LED ten digits: open-loop
vector
0: off 1: on
2: On at first power-up
LED Hundred: Reserved
LED thousands: Reserved
3110
〇
△
0x515
F5.22
Synchronous motor
pole search current
0.0%~400.0%
100.0%
〇
△
0x516
F5.30
Speed feedback or
encoder type
LED one digits: Encoder
type
0: ABZ encoder
1: Rotary transformer
LED ten digits: Encoder
direction
1000
〇
△
0x51E