Chapter 8 Functional Parameter Table
ACH200 Series High Voltage Variable Frequency Speed Control System Operating Manual
99
LED ten digits: over-
excitation control
0: Disable
1: Enable
LED
hundred
digits:
reserved
LED
thousand
digits:
reserved
FA.07
Busbar
overvoltage
suppression point
110.0%~150.0%
Model
Setting
※
〇
△
0xA07
FA.08
Bus overvoltage
suppression gain
0.0%~500.0%
10.0%
●
△
0xA08
FA.09
undervoltage
suppression
0: prohibited
1: enable
0
●
△
0xA09
FA.10
Undervoltage
suppression point
60.0% ~ 90.0%
80.0%
●
△
0xA0A
FA.11
Undervoltage
suppression
factor
0.0%~500.0%
100.0%
●
△
0xA0B
FA.12
Busbar
undervoltage
protection point
60.0%~90.0%
60.0%
※
〇
0xA0C
FA.13
Input protection
selection
LED one digits: rectifier side
overload protection switch
0: Closed 1: Open
LED ten digits: Input
overvoltage selector switch
0: Closed 1: Open
LED hundred digits: product
selection protection switch
0: Closed 1: Open
LED thousand digits: test
mode AC detection fault
selection
0: Closed 1: Open
1111
〇
0xA0D
FA.14
reservations
0: cloture
1: opens
0
〇
0xA0E
FA.15
Protection option
3
LED one digits: Output
phase loss protection
0: Off
1: On
2:
Slightly
unbalanced
output phase loss
LED ten digits: Input phase
loss protection
0x00XX: ten-digit value &
0x3
0: cloture
1: Software input phase loss
turn-on
(3-phase
AC
detection
+
bus
bar
fluctuation cycle detection)
2: Hardware input out-of-
phase on
0xXX: The ten-digit value is
1112
〇
0xA0F