Diagnostics and repair
LFXG-H Installation and Operation Guide
87
Table 5.8
CPU board LED summary
LED
Description
Normal condition
Error condition
Recommendation
Me
m
Memory
corruption
(EEPROMs
and FLASH)
OFF
1 blink: CPU
EEPROM
corrupt
2 blinks: Sensor
EEPROM
corrupt
3 blinks: Both
EEPROMs
corrupt
4 blinks: RAM
corrupt
5 blinks: Memory
mismatch
ON solid:
combination of
errors
Check software
diagnostics. Call
VEGA Field
Service.
HA
RT
HART
communicati
on indicator
ON
–
blinks when
receiving HART
messages
None
Check HART
device connection
on loop and HART
device functioning.
CP
U
Central
processing
unit on CPU
board
Blinks at rate of 1
time per second
LED does not
blink. CPU not
functioning.
Check power input.
Replace CPU
board.
Aux
Auxiliary
input
frequency
signal
indicator
Blinks if auxiliary
input present. OFF
if no auxiliary input
present
None
Check auxiliary
input wiring
terminals 11 and 12
with a meter for
frequency signal.
Check auxiliary
input equipment.
HV
Sensor high
voltage
ON
–
high voltage
is within
specification
OFF
–
high
voltage is
outside of
specification
Call VEGA Field
Service
Fiel
d
Radiation
field
indicator
Cycles in proportion
to radiation field
intensity at detector.
ON for 10 seconds
for each mR/hr,
then off for 2
seconds.
(Can use LED 5 that
blinks 1 time/sec to
time LED1 for field
indicator.)
None
Check for closed
source shutter,
buildup, and
insulation.
Содержание FiberFlex LFXG-H
Страница 2: ......
Страница 4: ...ii LFXG H Installation and Operation Guide NOTES...
Страница 6: ...iv LFXG H Installation and Operation Guide...
Страница 14: ...Preface xii LFXG H Installation and Operation Guide...
Страница 34: ...Installation 32 LFXG H Installation and Operation Guide FiberFlex mounting...
Страница 91: ...Diagnostics and repair LFXG H Installation and Operation Guide 89 Source Functions...
Страница 100: ...98 LSGH Installation and Operation Guide NOTES...
Страница 101: ......