Serial Interface Manual
•
TLS2 Monitoring Systems
Part No. 577013-767, Revision H
37
Function Code:
214
Version 5
Function Type:
In-Tank Mass/Density Inventory Report
Command Format:
Display:
<SOH>I214TT
Computer:
<SOH>i214TT
Typical Response Message, Display Format:
<SOH>
I214TT
04-30-09
2:18 PM
STATION HEADER 1....
STATION HEADER 2....
STATION HEADER 3....
STATION HEADER 4....
IN-TANK MASS INVENTORY
TC
TANK PRODUCT VOLUME MASS DENSITY OFFSET HEIGHT WATER TEMP
1 PRODUCT 1 7343 44521 45.35 -0.022 16.5 0.0 78.8
<ETX>
Typical Response Message, Computer Format:
<SOH>i214TTYYMMDDHHmmTTpssssNNFFFFFFFF...
TTpssssNNFFFFFFFF&&CCCC<ETX>
Notes:
1.
YYMMDDHHmm - Current Date and Time
2.
TT - Tank Number (Decimal, 00=all)
3.
p - Product Code (single ASCII character [20h-7Eh])
4.
ssss - Tank Status Bits:
Bit 1=(LSB) Delivery in Progress
Bit 2=Leak Test in Progress
Bit 3=Invalid Fuel Height Alarm (MAG Probes Only)
Bit 4-16 - Unused
5.
NN - Number of eight character Data Fields to follow (Hex)
6.
FFFFFFFF - ASCII Hex IEEE float:
1. Volume
2. Mass
3. Density
4. Height
5. Water
6. Temperature
7. TC Density
8. TC Volume
9. Ullage
10. Water Volume
11. Total TC Density Offset
7.
&& - Data Termination Flag
8.
CCCC - Message Checksum