Serial Interface Manual
•
TLS2 Monitoring Systems
Part No. 577013-767, Revision H
39
Function Code:
21C
Version 4
Function Type:
Power Outage Delivery Report
Command Format:
Display:
<SOH>I21CTT
Computer:
<SOH>i21CTT
Typical Response Message, Display Format:
<SOH>
I21CTT
29-07-08 14:58
STATION HEADER 1....
STATION HEADER 2....
STATION HEADER 3....
STATION HEADER 4....
POWER OUTAGE DELIVERY REPORT
TANK 1 PRODUCT 1
INCREASE DATE TIME VOLUME HEIGHT
END: 28-07-08 15:14 3231 32.21
START: 28-07-08 15:05 1244 12.22
AMOUNT: 1987
END: 25-07-08 14:48 4460 44.60
START: 25-07-08 14:37 1157 11.57
AMOUNT: 3303
<ETX>
Typical Response Message, Computer Format:
<SOH>i21CTTYYMMDDHHmmTTpddYYMMDDHHmmYYMMDDHHmmNNFFFFFFFF...
TtpddYYMMDDHHmmYYMMDDHHmmNNFFFFFFFF...&&CCCC<ETX>
Notes:
1.
YYMMDDHHmm - Current Date and Time
2.
TT - Tank Number (Decimal, 00 = all)
3.
p - Product Code (single ASCII character, from 20 Hex - 7E Hex)
4.
dd - Number of Deliveries to follow (Decimal, 00 if no data
available for this tank)
5.
YYMMDDHHmm - Starting Date/Time
6.
YYMMDDHHmm - Ending Date/Time
7.
NN - Number of eight character Data Fields to follow (Hex)
8.
FFFFFFFF - ASCII Hex IEEE float:
1. Starting Volume
2. Ending Volume
3. Starting Height
4. Ending Height
9.
&& - Data Termination Flag
10.