Serial Interface Manual
•
TLS2 Monitoring Systems
Part No. 577013-767, Revision H
42
Function Code:
231
Version 5
Function Type:
In-Tank Full Inventory Report
Command Format:
Display:
<SOH>I231TT
Computer:
<SOH>I231TT
Typical Response Message, Display Format:
<SOH>
I23100
16-06-11 07:35
STATION HEADER 1....
STATION HEADER 2....
STATION HEADER 3....
STATION HEADER 4....
FULL INVENTORY REPORT
TANK : 2 5 6
FULL VOLUME : 10000 10000 10000
VOLUME : 247 7433 1828
ULLAGE : 9753 2567 8172
HEIGHT : 5.8 16.7 11.4
WATER HEIGHT : 2.0 2.5 4.8
WATER VOLUME : 51 560 528
NET VOLUME : 196 6873 1300
TC VOLUME : 246 7366 1819
TC NET VOLUME : 195 6811 1294
TEMP : 64.5 72.0 66.1
MASS : - 45481 -
DENSITY : - 45.77 -
TC DENSITY : - 46.18 -
<ETX>
Typical Response Message, Computer Format:
<SOH>i231TTYYMMDDHHmmTTpssssNNFFFFFFFF...
TTpssssNNFFFFFFFF&&CCCC<ETX>
Notes:
1.
YYMMDDHHmm - Current Date and Time
2.
TT - Tank Number (Decimal, 00=all)
3.
p - Product Code (single ASCII character [20h-7Eh])
4.
ssss - Tank Status Bits:
Bit 1=(LSB) Delivery in Progress
Bit 2=Leak Test in Progress
Bit 3=Invalid Fuel Height Alarm (MAG Probes Only)
Bit 4-16 - Unused
5.
NN - Number of eight character Data Fields to follow (Hex)
6.
FFFFFFFF - ASCII Hex IEEE float:
1. Volume
2. TC Volume
3. Ullage
4. Height
5. Water
6. Temperature
7. Water Volume
8. Full Volume
9. Net Volume
10. TC Net Volume
11. Mass
12. Density
13. TC Density
7.
&& - Data Termination Flag
8.
CCCC - Message Checksum